The E7 Drive is designed exclusively for Commercial HVAC applications. All features are designed for this purpose, including Building Automation communications. Metasys N2, APOGEE FLN and Modbus are embedded. EtherNet/IP, Modbus TCP/IP and LonWorks are plug-in options. The drive is plenum rated for variable torque applications. Anti-windmilling, motor preheat, energy-savings, and PI setpoint control are standard. Many options are available.

For more information regarding our 18-Pulse design for low total harmonic

distortion please review our E7 18-Pulse Drive News Release or our E7 18-Pulse Drive Flyer.

 

 

 

 


 

 

208vAC:


Rated Input Voltage
Drive Model Number
Rated Output Current
(Amps)
Nominal HP2
Standard Enclosure
208V
3.6
1/2
NEMA 1
3/4
208V
4.6
1
NEMA 1
7.8
2
10.8
3
16.8
5
208V
31.0
7.5
NEMA 1
10
208V
46.2
15
NEMA 1
59.4
20
208V
74.8
25
NEMA 1
88.0
30
115
40
208V
162
50
Protected Chassis
192
60
208V
215
75
Protected Chassis
312
100
208V
360
125
Protected Chassis
415
150


240vAC:

Rated Input Voltage
Drive Model Number
CIMR-E7U
Rated Output Current
(Amps)
Nominal HP2
Standard Enclosure
240V
3.6
1/2
NEMA 1
3/4
240V
4.6
1
NEMA 1
7.8
2
240V
10.8
3
NEMA 1
16.8
5
240V
23.0
7.5
NEMA 1
31.0
10
240V
46.2
15
NEMA 1
59.4
20
240V
74.8
25
NEMA 1
88.0
30
115
40


230vAC:

Rated Input Voltage
Drive Model Number
CIMR-E7U
Rated Output Current
(Amps)
Nominal HP2
Standard Enclosure
230V
162
50
Protected Chassis
60
230V
192
75
Protected Chassis
230V
312
100
Protected Chassis
125
230V
360
150
Protected Chassis

 

480vAC:


Rated Input Voltage
Drive Model Number
CIMR-E7U
Rated Output Current
(Amps)
Nominal HP2
Standard Enclosure
480V
1.8
1/2
NEMA 1
3/4
480V
2.1
1
NEMA 1
3.7
2
5.3
3
480V
7.6
5
NEMA 1
12.5
7.5
17.0
10
480V
21.0
15
NEMA 1
27.0
20
34.0
25
480V
40.0
30
NEMA 1
52.0
40
67.2
50
480V
77.0
60
NEMA 1
96.0
75
125
100
480V
156
125
Protected Chassis
180
150
480V
240
200
Protected Chassis
304
250
480V
414
300
Protected Chassis
350
480V
515
400
Protected Chassis
450
480V
675
500
Protected Chassis

  1. For single-phase input, select the drive by ensuring that 50% of the drive's continuous output current rating is equal to or greater than the motor's full load amp rating
  2. Horsepower rating is based on standard NEMA B 4-pole motor design and NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors
  3. These drives have a minimum 12 week lead-time. For faster delivery, use CIMR-E7U22P21 or CIMR-E7U42P21.